Fruit and Vegetable Vacuum Cooler Application Technology Analysis: Principles, Selection and Practical Data

I. How Vacuum Precooling Actually Works

Place freshly harvested fruits and vegetables into a sealed vacuum chamber and evacuate the air. When the pressure drops to below 600Pa, moisture on the surface of the fruits and vegetables begins to evaporate at low temperature. For every 1% of moisture evaporated, the temperature drops by approximately 6℃. In 30–50 minutes, the temperature can drop from 25–35℃ to 0–2℃.

Key: Vacuum precooling does not "freeze" the product; it is "evaporative cooling". The moisture loss rate is controlled at 2–3%.

II. Core System Composition

2.1 Vacuum System

The vacuum pump draws the pressure down to below 600Pa. Leybold rotary vane pumps are used, with dual pumps in parallel for large models.

2.2 Refrigeration System — Water Catcher

The water catcher is essentially an evaporator; its surface temperature is maintained at 5–10℃, and water vapor condenses into water and is discharged. A vacuum precooler must have a refrigeration system.

2.3 Control System

PLC-controlled, automatically running the entire cycle. The core is pressure control — evacuate to the set pressure → maintain the pressure range → the product reaches the target temperature → break the vacuum and discharge.

III. CVF Series Model Selection Parameters

Model Processing Capacity Power Compressor Vacuum Pump
CVF-1000A-2P 1000kg 39.9kW Bitzer 30.7kW Leybold 5.5kW
CVF-2000E-4P 2000kg 77.8kW Hanbell 61.6kW 11kW
CVF-3000-6P 3000kg 89.3kW Hanbell 61.6kW 22.5kW
CVF-4000W-10P 4000kg 99.7kW Hanbell 73.2kW 7.5kW×2+Roots

IV. Cooling Processes for Different Product Categories

Category Loading Capacity Cooling Time Moisture Loss Rate Target Temperature
Leafy Vegetables 6–8kg/m² 25–40min 1.5–3% 0–2°C
Edible Fungi 5–7kg/m² 20–35min 1–2% 0–2°C
Flower and Fruit Vegetables 8–10kg/m² 30–50min 2–3.5% 2–5°C

V. Comparison with Other Precooling Methods

Method Cooling Time Moisture Loss Rate Investment Cost
Vacuum Precooling 20–40min 1.5–3% Medium-High
Forced-Air Cooling 4–12h 3–5% Low
Cold Water Precooling 30–60min 0–1% Medium
Cold Storage 12–24h 5–10% Medium

Yuanxian Machinery | www.yuanxianmachinery.com