CVF-1000A-2P Technical Proposal: Copeland Scroll, R404A, Leybold SV300

Key takeaways
The CVF-1000A-2P is a two-pallet produce vacuum pre-cooler with an 8.0 m³ vacuum chamber and 1000 kg per cycle. One Copeland scroll ZB220KQE (27.8 kW) with R404A delivers about 82.6 kW of cooling, and a German Leybold SV300 vacuum pump at 7.5 kW pulls the chamber to 600 Pa or less, so the 30–40 minute cycle brings produce to 0–10°C with 1.0–2.0% weight loss. The unit is built for the Canadian market on 600 V / 60 Hz / 3P, draws a maximum of about 86 A (200 A breaker recommended) with a compressor starting current of about 218 A, and weighs 7800 kg at L4600 × W2200 × H2600 mm.

Version: 2026-08-04 | Model: CVF-1000A-2P (2 pallets / 1000 kg class)
Export destination: Canada | Power supply: 600 V / 60 Hz / 3P (North American standard)
Compressor: Copeland scroll ZB220KQE × 1 | Refrigerant: R404A | Vacuum pump: Leybold SV300 (Germany)


1. Project Design Summary

This project is a vacuum pre-cooling installation for rapid vegetable cooling, with an 8.0 m³ vacuum chamber and a 1000 kg capacity, designed to raise production efficiency and extend shelf life, with a pre-cooling temperature of 0–10°C.

Vacuum pre-cooling works on the physical principle that the boiling point of water falls as pressure drops: vegetables are placed in the vacuum chamber and the air is evacuated, and when the pressure reaches the set point the surface moisture begins to evaporate, carrying heat out of the product so that the vegetables cool evenly inside and out to the 2–5°C fresh-keeping temperature.

Functions unique to vacuum pre-cooling:

  • Surface water removal: vegetables harvested in the rain can have surface water removed
  • Healing function: small surface wounds on vegetables “heal”, reducing the chance of microbial entry
  • Even cooling: vegetables cool inside and out at the same time, with no “cold outside, warm inside” dead zones

2. Construction Scale

ItemSpecification
Pre-cooler external dimensionsL4600 × W2200 × H2600 mm (subject to final design)
Vacuum chamber internal dimensionsL2600 × W1400 × H2200 mm
Vacuum chamber materialQ235 carbon steel, 6.0 mm thick, painted inside and out, washable with a high-pressure hose
Door systemManual sliding door (single door all-in-one unit)
Equipment structureAll-in-one, single door

3. Design Parameters

ParameterValue
Summer outdoor design dry bulb temperature (TWK)27 °C
Summer air conditioning outdoor design daily mean wet bulb temperature (TWS)28 °C
Condenser condensing temperature40 °C
Evaporating temperature-5 °C

4. Technical Specifications

No.ItemSpecification / modelRemarks
1Chamber volume8.0 m³L2600×W1400×H2200 mm, carbon steel 6 mm
2Capacity per cycle1000 kgDepends on the product
3Processing time per cycle30–40 minutesDepends on the product
4Cooling capacityabout 82.6 kW71000 kcal/h
5Operating powerabout 40 kWReference value, subject to final design
6CompressorCopeland scroll ZB220KQE, 27.8 kW × 1R404A version, 600 V/60 Hz/3P (60 Hz North American version)
7RefrigerantR404AEnvironmentally friendly refrigerant, ODP = 0
8Vacuum pumpLeybold SV300, 7.5 kWGerman import, about 300 m³/h
9CondenserAir-cooled (water-cooled / evaporative optional)Zhejiang Rongyi FNH200, 1.5 kW × 2
10Power supply600 V / 60 Hz / 3P (Canadian standard)Auxiliary control circuit 220 V/60 Hz/1P
11Maximum operating currentabout 86 A200 A breaker recommended
12Compressor starting currentabout 218 A
13Equipment weight7800 kgEstimate, subject to actual
14Overall dimensionsL4600 × W2200 × H2600 mmSubject to final design dimensions
15Ultimate vacuum≤ 600 Pa
16Final produce temperature0–10 °CFresh-keeping range 2–5°C, adjustable
17Weight loss1.0–2.0%Varies slightly with vegetable variety
18Noiseabout 70 dBSlightly louder when breaking vacuum

5. Core Configuration List

No.ItemBrandOriginQtyUnit
1Refrigeration system (compressor)Copeland ZB220KQEUSA1set
2Vacuum pump systemLeybold SV300Germany1set
3Water catcher systemYuanxian MachineryDongguan1set
4RefrigerantR404AChina1batch
5Condenser (air-cooled)RongyiZhejiang2set
6Electrical cabinetYuanxian MachineryDongguan1set
7Microcomputer control systemLSKorea1set
8HMI operating systemWeinviewTaiwan1set
9Carbon steel vacuum chamberYuanxian MachineryGuangdong1set
10Pneumatic control systemAirTACZhejiang1set
11Temperature detection systemLSKorea1set
12Door system (manual sliding door)Yuanxian MachineryDongguan1set

6. Why These Components

1. Why a Copeland scroll compressor

ItemCopeland scroll ZB220KQE (this proposal)Copeland scroll 14.12 kW × 2 (twin)
ModelZB220KQE × 1 unitZB114 class × 2 in parallel
Power27.8 kW28.24 kW (14.12 × 2)
StructureSingle unit, simple systemTwin units in parallel
Cooling capacityabout 82.6 kWabout 82.6 kW
CostLower (1 compressor + 1 circuit)Higher (2 units + dual circuits)
MaintenanceSingle-machine maintenance, single spare parts setSpares for two machines
Fault toleranceNo redundancy, stops on failureMutual standby, one failure allows reduced-load operation
  • A single ZB220KQE (27.8 kW) covers the 1000 kg / 30–40 minute cooling duty with the same cooling capacity as the twin option, but a simpler system and lower cost
  • Verified knowledge base case: Mr Tang's two-pallet pre-cooler in Neijiang, Sichuan uses a single Copeland ZB220KQ (R22 version) with a domestic Dalutong vacuum pump and a water-cooled condenser, and that configuration has been delivered and is running

2. Why R404A refrigerant

  • Environmental compliance: R404A is an HFC refrigerant with an ODP (ozone depletion potential) of 0, in line with international environmental trends
  • Export compatibility: markets in Europe, North America and Southeast Asia restrict R22 (an HCFC) strictly, while R404A faces no phase-out pressure
  • Performance match: it is a mature match with Copeland scroll compressors at a -5°C evaporating temperature

3. Why a Leybold SV300 vacuum pump (export to Canada)

  • Pumping capability: Leybold SV300, pumping speed about 300 m³/h, 7.5 kW, the standard configuration for the 1000 kg class (knowledge base vacuum pump selection reference: 1000 kg = 1 × SV300)
  • Canadian precedent: the Canadian EV three-pallet project uses a Leybold SV300 (480 V/60 Hz/3P with a transformer); Mr Zhang's two-pallet project in Canada uses an imported pump of the same class
  • Export reliability: a German brand with a developed North American service network and high customer recognition
  • Power compatibility: the 60 Hz version suits the Canadian 600 V/60 Hz/3P supply (large machines can use a transformer to step down to 480 V)

4. Power supply adaptation (export to Canada)

  • Main supply: 600 V / 60 Hz / 3P (Canadian industrial standard)
  • Auxiliary control circuit: 220 V / 60 Hz / 1P (stepped down from 600 V by a control transformer)
  • Knowledge base precedents: Mr Zhang in Canada (600 V/60 Hz/3P, Bitzer compressor + Busch pump), Canadian EV (600 V/60 Hz/3P, 2 × Leybold SV300), ChangL in the USA (600 V/60 Hz/3P, Copeland ZB76KQE) — the Copeland ZB series in North American 60 Hz versions already has a delivery record
  • Note the frequency difference: 60 Hz versions of the compressor, pump and fan must be selected for 60 Hz; a 50 Hz machine cannot be used directly (speed and cooling capacity both differ)

5. Vacuum pump selection rule

A Roots pump needs a backing pump to reach 1 kPa before it starts. This machine targets 600 Pa, which a single-stage vane pump satisfies, so no Roots pump is needed. Only large produce pre-coolers (≥10P / CVF-5000+) are fitted with Roots pumps.

7. Pricing and Payment

Equipment price and payment terms are quoted per project and confirmed in the formal contract. Contact sales@vacuum-fresh.com for a current quotation.

  • Delivery within China
  • One year of free warranty service
  • Includes freight (standard delivery), installation and training
  • Excludes unloading and lifting (the customer places the unit in position)
  • Equipment only; water, electricity and civil works (including drilling) are provided by the customer

8. Installation and Commissioning

Customer responsibilities

  • The power line from the main supply to the equipment control cabinet is installed by the customer
  • Air exhaust, drainage and the associated concrete civil works are provided by the customer
  • Unloading, moving, positioning and levelling of the equipment on arrival are the customer's responsibility

Supplier responsibilities

  • The supplier transports the equipment to the customer site, including installation, training and freight
  • The supplier arranges personnel to supervise lifting and positioning on site
  • Personnel are dispatched to install and commission within 2 days of arrival
  • Estimated installation time for the single unit is about 5 days
  • Acceptance can be carried out once installation and commissioning are complete

9. After-Sales Service Commitment

Response stageTime limit
Telephone responseImmediate response on receipt of fault information
Solution providedWithin 8 hours
On-site arrival where remote support is insufficientWithin 48–72 hours
Fault cleared on siteNot exceeding 72 hours
  • One year warranty on the complete machine
  • During the warranty period: faults caused by supplier design or manufacture are repaired free of charge
  • After the warranty period: lifetime preferential technical support, the most favourable spare parts and after-sales service

Proposal data sources: Yuanxian Machinery knowledge base CVF-1000A-2P domestic pump proposal (2026-05-09), Copeland produce pre-cooling selection, CVF-1000-2P high-specification proposal

Frequently Asked Questions

Why a single Copeland ZB220KQE instead of two smaller compressors?

One 27.8 kW ZB220KQE covers the 1000 kg / 30–40 minute duty with the same 82.6 kW as the twin-compressor option (2 × 14.12 kW), but with a simpler system and lower cost. The trade-off is no redundancy.

Why R404A rather than R22 for an export machine?

R404A is an HFC refrigerant with an ODP of 0, so it faces no phase-out pressure in Europe, North America or Southeast Asia, and it matches the Copeland scroll compressor well at a -5°C evaporating temperature.

Does the CVF-1000A-2P need a Roots pump to reach 600 Pa?

No. A Roots pump needs a backing pump to reach 1 kPa before it starts; with a 600 Pa target a single-stage vane pump is sufficient. Only large produce pre-coolers of 10 pallets and above (CVF-5000+) use Roots pumps.